E18
DuroMax Reverse Power / Backfeed Detection

Control panel shows E18, generator shuts down shortly after transfer to load

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Incorrect ATS wiring causing utility to backfeed generator, Stuck or welded ATS contacts, Misconfigured phase rotation or sensing, Faulty reverse power relay in controller

How to Fix / Troubleshooting

Safety first: Immediately open the main utility breaker and the generator breaker. Backfeeding can be deadly. Only qualified personnel should work inside the ATS.

  • Inspect ATS wiring: With all power off, open the ATS and verify that utility, generator, and load conductors are landed on the correct terminals per the DuroMax wiring diagram.
  • Check contactor operation: Manually operate the ATS contactor (if possible) and ensure it fully transfers between utility and generator positions without bridging both sources.
  • Test for welded contacts: Use a meter to confirm that when in generator position, there is no continuity between utility and load terminals. Replace the ATS contactor if contacts are welded.
  • Verify phase rotation (3‑phase units): Ensure phase sequence from generator matches the ATS and load. Incorrect rotation can cause protection trips.
  • Controller check: If wiring and ATS hardware are correct, the reverse power sensing circuit in the controller may be faulty and require professional diagnosis.
Advertisements

Repair Difficulty

Professional Required 5/5

Required Part

Automatic Transfer Switch Contactor