DuroStar Nuisance Start/Stop Cycling

Generator starts and stops repeatedly in AUTO mode without transferring load.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Incorrect utility voltage sensing thresholds, Loose utility sense wiring, Unstable utility power, Faulty ATS control board

How to Fix / Troubleshooting

Safety first: Lock out the main utility breaker and ensure only qualified personnel access the ATS and control wiring.

  • Review controller settings: Check the DuroStar controller's utility voltage and frequency thresholds and delays. Adjust to recommended values.
  • Inspect sense wiring: Tighten all utility sense connections at the generator and ATS.
  • Monitor utility power: Use a power quality meter to check for frequent sags or outages. Coordinate with the utility if supply is unstable.
  • Test ATS board: If wiring and settings are correct, the ATS control board may be intermittently signaling start/stop and should be tested or replaced.
Advertisements

Repair Difficulty

Professional Required 5/5

Required Part

Automatic Transfer Switch Control Board
Check Price on Amazon