AL24
FG Wilson Alternator Overtemperature Protection

Controller shows AL24 – Alternator Temperature High (if stator RTD fitted)

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Blocked alternator ventilation, Overload operation, High ambient temperature with inadequate cooling, Faulty temperature sensor

How to Fix / Troubleshooting

Safety first: Stop the generator and allow the alternator to cool. Isolate battery negative before opening covers.

  • Inspect ventilation: Check that alternator air inlets and outlets are not blocked by debris or insulation.
  • Check load history: Review recent load levels; continuous operation near or above rated kVA can overheat the alternator.
  • Inspect temperature sensor wiring: Locate the stator RTD or thermistor leads in the terminal box and check for damage or loose connections.
  • Reduce load: If the application allows, reduce the continuous load to within 80–90% of rated capacity.
  • Professional testing: If overheating persists, have the alternator tested for internal faults or partial shorted turns.
Advertisements

Repair Difficulty

Hard 4/5

Required Part

Alternator Stator Temperature Sensor