FG Wilson
False Start Command / Spurious Auto Start
Generator starts unexpectedly without apparent mains failure
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Faulty mains sensing circuit, Incorrect controller settings (test mode), Shorted remote start contacts, ATS miswiring
How to Fix / Troubleshooting
Safety first: Treat the generator as capable of starting at any time. Disable AUTO mode before investigation.
- Check controller event log: Review start reasons (mains failure, remote start, test) in the controller history.
- Inspect remote start input: Verify that remote start terminals are not shorted by damaged wiring or water ingress.
- Verify mains sensing: Confirm that the controller sees correct mains voltage and frequency; unstable mains may trigger starts.
- Review settings: Ensure no periodic test mode is enabled unintentionally.
Advertisements
Repair Difficulty
Medium
3/5
Required Part
Remote Start Control Wiring
Check Price on Amazon
We may earn a commission from links on this page.
Advertisements