Controller displays E09 and the generator will not start in AUTO mode, even during a utility power outage.
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Possible Causes
How to Fix / Troubleshooting
Safety first: Turn OFF the generator and lock out the ATS if possible. Only qualified persons should open the ATS cabinet due to live utility connections.
- Check low-voltage control cable: Inspect the multi-conductor control cable between the Firman standby generator and the ATS. Look for physical damage, crushed sections, or rodent chewing. Repair or replace damaged cable.
- Verify terminal connections: With power isolated where possible, tighten all low-voltage control terminals at both the generator control board and the ATS control block. Loose screws can cause intermittent E09 errors.
- Inspect ATS position switches: Many ATS units use micro-switches to indicate NORMAL or EMERGENCY position. Check that the actuator cams are engaging the switches and that the switch wiring is intact.
- Confirm wiring per Firman diagram: Compare the installed wiring to the Firman ATS wiring schematic for your model. Correct any mis-landed wires.
If E09 persists, the ATS control board or the generator controller may require professional testing and possible replacement.