GE Failure to Stop / Continuous Run

Generator runs continuously and does not shut down after utility power returns

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Stuck run relay on control board, ATS not signaling utility return, Faulty utility sensing circuit, Controller programmed in manual mode

How to Fix / Troubleshooting

Safety First: Verify that utility power is stable and present. Use proper lockout/tagout before working in the ATS or control panel.

  • 1. Check controller mode: Ensure the GE controller is set to AUTO, not MANUAL/TEST. In manual mode, the unit will not stop automatically.
  • 2. Verify utility sensing: Confirm the controller indicates utility is present. If not, troubleshoot utility sensing fuses and wiring.
  • 3. Observe ATS position: Check if the ATS has re-transferred to utility. If not, see ATS-related faults.
  • 4. Force stop: Use the OFF button on the controller to stop the generator. If it continues to run, immediately disconnect the negative battery cable and contact a technician; a stuck run relay or wiring fault is likely.