Sensor Fault
Generac Engine monitoring sensor failure

Controller shows 'Sensor Fault' or identifies a specific sensor (oil temp, coolant temp, etc.) as failed.

Advertisements

Possible Causes

Open or shorted sensor, Damaged sensor wiring, Incorrect sensor type installed, Controller input failure

How to Fix / Troubleshooting

Safety: Turn the generator OFF and disconnect battery power before unplugging sensors.

  • Identify sensor: Use the controller display or manual to determine which sensor is faulted (e.g., coolant temp, oil temp).
  • Inspect connector and wiring: Check for corrosion, loose pins, or damaged insulation. Clean and reseat connectors.
  • Test sensor: Measure sensor resistance at ambient temperature and compare to Generac specifications. Replace the sensor if readings are out of range or open/shorted.
  • Controller input: If a known-good sensor still reads faulty, the controller input circuit may be damaged. Replace the controller.
Advertisements

Repair Difficulty

Easy 2/5

Required Part

Coolant Temperature Sensor