E15
Genergy Low Fuel Pressure Under Load

Generator shuts down and displays E15; controller logs indicate low fuel pressure or starvation during operation.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Undersized gas line to Genergy unit, Partially closed manual gas valve, Clogged gas filter or regulator, Failing gas pressure regulator

How to Fix / Troubleshooting

Safety first: Turn the generator OFF and close the gas supply valve. Work with a licensed gas technician when modifying gas piping.

  • Verify gas line sizing: Compare the installed gas line diameter and length to the Genergy installation manual. Long runs or small pipe can cause pressure drop under load.
  • Check valves and filters: Ensure all inline gas valves are fully open. Replace or clean any inline gas filters according to manufacturer instructions.
  • Inspect regulator: Check the Genergy‑supplied regulator for frost, contamination, or damage. Ensure the vent is clear. Replace the regulator if outlet pressure cannot be maintained.
  • Measure dynamic pressure: With a manometer and under technician supervision, measure gas pressure at the generator inlet while running under load. Compare to Genergy specifications.
  • Correct supply issues: If utility or tank pressure is inadequate, coordinate with the gas supplier to correct the issue.
Advertisements

Repair Difficulty

Professional Required 5/5

Required Part

Gas Regulator
Check Price on Amazon

We may earn a commission from links on this page.

Advertisements