E15
Genergy
Low Fuel Pressure Under Load
Generator shuts down and displays E15; controller logs indicate low fuel pressure or starvation during operation.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Undersized gas line to Genergy unit, Partially closed manual gas valve, Clogged gas filter or regulator, Failing gas pressure regulator
How to Fix / Troubleshooting
Safety first: Turn the generator OFF and close the gas supply valve. Work with a licensed gas technician when modifying gas piping.
- Verify gas line sizing: Compare the installed gas line diameter and length to the Genergy installation manual. Long runs or small pipe can cause pressure drop under load.
- Check valves and filters: Ensure all inline gas valves are fully open. Replace or clean any inline gas filters according to manufacturer instructions.
- Inspect regulator: Check the Genergy‑supplied regulator for frost, contamination, or damage. Ensure the vent is clear. Replace the regulator if outlet pressure cannot be maintained.
- Measure dynamic pressure: With a manometer and under technician supervision, measure gas pressure at the generator inlet while running under load. Compare to Genergy specifications.
- Correct supply issues: If utility or tank pressure is inadequate, coordinate with the gas supplier to correct the issue.