E16
Genergy Emergency Stop Circuit Active

Generator will not start; E16 indicates an emergency stop or remote stop condition.

Advertisements

Possible Causes

Engaged emergency stop button on generator enclosure, Open contact in remote E‑stop circuit, Broken wire in safety loop, Faulty E‑stop switch

How to Fix / Troubleshooting

Safety first: Confirm that it is safe to allow the generator to run before resetting any emergency stop devices.

  • Check local E‑stop: Locate the red emergency stop button on the Genergy enclosure. If it is pressed in, twist or pull (depending on design) to reset.
  • Inspect remote E‑stop stations: If your system has remote emergency stop buttons, verify none are engaged. Reset as required.
  • Test continuity of E‑stop loop: With power off, use a multimeter to check continuity across the E‑stop circuit terminals at the controller. An open circuit indicates a wiring break or failed switch.
  • Repair wiring: Trace the E‑stop cable for damage, especially at entry points and junction boxes. Repair or replace damaged sections.
  • Replace faulty switch: If a switch does not close when reset, replace it with a Genergy‑approved emergency stop switch.
Advertisements

Repair Difficulty

Easy 2/5

Required Part

Emergency Stop Switch
Check Price on Amazon