E20
Genergy
Underfrequency Under Load
Generator runs but E20 is displayed; controller indicates low frequency (Hz) under load.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Overloaded generator, Weak engine output, Governor droop misadjusted, Fuel restriction at higher demand
How to Fix / Troubleshooting
Safety first: Open the generator output breaker to remove load before making adjustments. Do not work on live circuits.
- Assess load: Compare total connected load to the Genergy generator's kW rating. Shed non‑critical loads and avoid starting large motors simultaneously.
- Check air and fuel filters: Replace clogged air filters and gas filters. Restricted flow can cause the engine to slow under load.
- Inspect governor linkage: Ensure there is no binding and that the governor spring is correctly installed. Adjust droop or gain settings only according to the Genergy service manual.
- Test under step loads: Reapply loads gradually while monitoring frequency. If frequency still drops excessively, engine performance testing (compression, ignition) may be required.