Guardian
Transfer Switch Fails to Transfer
Generator starts automatically on power loss but transfer switch does not move to generator position; house remains on utility or dark.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Failed transfer switch coil or motor, Mechanical binding in contactor, Control wiring fault from generator to ATS, Interlock or safety switch engaged
How to Fix / Troubleshooting
Safety first: Only qualified persons should open and work inside transfer switches. Turn off all power sources and verify with a meter before touching conductors.
- Listen for operation: During an outage test, listen for the ATS contactor to move. No sound suggests a coil or control issue.
- Inspect control cable: Check the low-voltage control cable between the Guardian generator and ATS for damage or loose connections.
- Manual operation test: With all power off, attempt to manually operate the contactor (if design allows) to check for mechanical binding.
- Coil voltage check: During a start command, measure coil voltage at the ATS. If present but no movement, replace the contactor assembly.
Advertisements
Repair Difficulty
Professional Required
5/5
Required Part
Automatic Transfer Switch Contactor Coil