E07
Himoinsa
Starter Motor Circuit Fault
Generator controller indicates E07 and the engine does not crank when a start command is given.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Faulty starter solenoid, Worn starter motor, Defective start relay in Himoinsa control panel, Broken wiring in start circuit
How to Fix / Troubleshooting
Safety: Isolate battery negative before working on the starter circuit. Ensure the generator cannot start automatically.
- Listen for solenoid click: Attempt a start while listening near the engine. If there is no click, the solenoid may not be energised.
- Check start relay: In the Himoinsa control panel, locate the start relay (refer to wiring diagram). Verify coil voltage when a start is commanded. Replace the relay if the coil is energised but contacts do not close.
- Inspect wiring: Check cables from the relay to the starter solenoid for continuity and tight connections. Look for burnt or loose terminals.
- Test solenoid and starter: With battery connected and using proper precautions, measure voltage at the solenoid terminal during a start attempt. If voltage is present but the starter does not engage, the solenoid or starter motor is likely faulty and should be replaced.
- Re-test system: After repairs, clear E07 on the controller and perform several start/stop cycles to confirm reliable operation.