E10
Himoinsa Remote Start Signal Fault / ATS Communication Error

Controller shows E10 and the generator will not start in automatic mode from the ATS.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Open circuit in remote start terminals, Incorrect ATS wiring to Himoinsa controller, Faulty ATS dry contact, Misconfigured controller input type

How to Fix / Troubleshooting

Safety: Isolate both generator and ATS control power before opening panels. Follow lockout/tagout procedures.

  • Verify remote start wiring: In the Himoinsa control panel, locate the remote start terminals (e.g., RS+, RS- or similar). Confirm continuity of the cable to the ATS using a multimeter.
  • Check ATS contacts: In the ATS, identify the dry contact designated for generator start. Verify that it closes when mains fails. Replace the contact block if it does not operate correctly.
  • Confirm input configuration: In the controller settings, ensure the remote start input is configured for the correct logic (NO/NC) as per the ATS design.
  • Simulate start signal: Temporarily bridge the remote start terminals at the generator (if safe and allowed by the manual) to see if the unit starts. If it does, the issue is in the ATS or wiring. If not, the controller input may be faulty.
  • Restore and test: After corrections, restore power, clear E10, and perform a full mains-fail test to confirm automatic starting.
Advertisements

Repair Difficulty

Medium 3/5