E12
Himoinsa Generator Undervoltage Protection

Controller shows E12 and the generator does not accept load from the ATS.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Incorrect AVR voltage setting, Faulty Automatic Voltage Regulator (AVR), Loose stator winding connections, Shorted stator winding

How to Fix / Troubleshooting

Safety: Isolate generator from load and mains. Turn OFF and lock out the unit before opening the alternator terminal box.

  • Check voltage reading: With the generator running unloaded, read phase-to-phase voltage on the controller and with a multimeter. Compare to the nameplate rating (e.g., 400 V).
  • Inspect AVR settings: Locate the AVR in the alternator terminal box. Adjust the voltage potentiometer slightly while monitoring voltage. Do not exceed rated voltage.
  • Inspect connections: Tighten all stator and AVR wiring terminals. Look for signs of overheating or discoloration.
  • Test AVR: If voltage remains low or unstable, replace the AVR with a compatible Himoinsa-specified unit.
  • Stator test (advanced): With power off, perform insulation resistance and winding resistance tests on the stator. If readings are abnormal, the alternator may require rewinding or replacement by a specialist.
Advertisements

Repair Difficulty

Hard 4/5

Required Part

Automatic Voltage Regulator (AVR)