E13
Himoinsa Generator Overvoltage Protection

Generator controller displays E13 and trips off load during operation.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

AVR failure causing runaway voltage, Incorrect AVR sensing wiring, Loose or broken voltage sensing leads, Incorrect controller voltage settings

How to Fix / Troubleshooting

Safety: Disconnect generator from load and shut it down. High voltage can damage equipment and cause electric shock.

  • Verify voltage: With the generator running unloaded, measure output voltage with a calibrated multimeter. Confirm if it exceeds rated value.
  • Inspect AVR wiring: Check the sensing leads from the alternator to the AVR for correct connection and tightness. Refer to the Himoinsa alternator wiring diagram.
  • Check controller settings: Ensure the nominal voltage and overvoltage thresholds in the controller match the generator rating.
  • Replace AVR if necessary: If voltage remains uncontrollable or drifts high despite correct wiring, replace the AVR with the correct Himoinsa-specified model.
  • Test under load: After repair, run the generator and gradually apply load while monitoring voltage and confirming E13 does not reoccur.
Advertisements

Repair Difficulty

Hard 4/5

Required Part

Automatic Voltage Regulator (AVR)