E16
Himoinsa High Alternator Winding Temperature

Controller shows E16 and the generator shuts down after running for some time.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Blocked alternator ventilation, Overload beyond rated kVA, Faulty alternator temperature sensor, High ambient temperature with inadequate cooling

How to Fix / Troubleshooting

Safety: Allow the generator to cool before touching the alternator. Isolate from load and mains.

  • Check load level: Review the kW/kVA load on the controller. Ensure it does not exceed the Himoinsa generator rating. Reduce non-essential loads if necessary.
  • Inspect ventilation: Ensure air inlets and outlets on the canopy are clear. Remove debris and clean filters or grilles.
  • Inspect alternator: Check for dust buildup on the alternator housing and cooling fan. Clean with dry compressed air.
  • Check temperature sensor: Locate the alternator winding temperature sensor. Inspect wiring and test sensor resistance vs. temperature. Replace if readings are incorrect.
  • Test under reduced load: Restart the generator with a lower load and monitor temperature alarms. Persistent E16 may indicate internal alternator issues requiring specialist service.
Advertisements

Repair Difficulty

Medium 3/5

Required Part

Alternator Temperature Sensor
Check Price on Amazon

We may earn a commission from links on this page.

Advertisements