E18
Himoinsa Phase Sequence / Rotation Error

Controller shows E18 and the generator breaker does not close to supply load.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Incorrect phase wiring at alternator terminals, Wrong connection at ATS output, Controller phase rotation setting mismatch, Reversed CT or VT connections

How to Fix / Troubleshooting

Safety: Isolate generator and ATS from mains and load. Verify absence of voltage before touching terminals.

  • Verify phase order: Using a phase rotation meter, check the phase sequence at the generator output terminals (L1, L2, L3). It should match the installation design.
  • Inspect wiring: Compare actual wiring to the Himoinsa wiring diagram. Correct any swapped phases at the alternator or breaker.
  • Check ATS connections: Ensure the ATS input from the generator maintains the same phase order through to the load.
  • Controller settings: Confirm the controller is configured for the correct phase rotation (e.g., ABC). Adjust if necessary according to the manual.
  • Test breaker closure: After corrections, clear E18 and attempt to close the generator breaker under no-load conditions, then test with load.
Advertisements

Repair Difficulty

Hard 4/5

Required Part

Generator Output Wiring Harness
Check Price on Amazon

We may earn a commission from links on this page.