E23
Himoinsa
Earth Fault / Ground Fault Protection
Generator controller indicates E23 and the unit trips off load intermittently.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Insulation breakdown in cables, Moisture ingress in junction boxes, Incorrect neutral-earth bonding, Faulty earth fault relay or CT
How to Fix / Troubleshooting
Safety: Isolate generator and all downstream circuits. Use appropriate PPE when testing insulation.
- Inspect cables and junctions: Look for damaged insulation, water ingress, or contamination in cable terminations and junction boxes.
- Insulation resistance test: Use a megohmmeter to test insulation between phases and earth, and neutral and earth. Identify and repair low-resistance circuits.
- Check bonding: Verify that neutral-earth bonding is configured as per Himoinsa installation guidelines (TN, TT, etc.). Incorrect bonding can cause nuisance trips.
- Test earth fault relay: If fitted, test the earth fault relay and associated CT by injecting a test current. Replace faulty components.
- Re-test under load: After repairs, run the generator and gradually apply load while monitoring for E23.