E26
Himoinsa
Preheat / Glow Plug Fault (Cold Start Failure)
Controller shows E26 and the generator shuts down shortly after start, with white smoke from exhaust.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Failed glow plugs, Faulty preheat relay, Broken preheat wiring harness, Controller preheat timer misconfiguration
How to Fix / Troubleshooting
Safety: Turn OFF generator and isolate battery before working on preheat circuits.
- Check preheat operation: Observe the preheat indicator on the controller during a start attempt. If it does not activate, suspect relay or control issues.
- Test glow plugs: Measure resistance of each glow plug with a multimeter. Replace any open-circuit or high-resistance plugs.
- Inspect preheat relay: Locate the preheat relay in the control panel. Check for coil voltage during preheat. Replace if the relay does not close.
- Verify wiring: Inspect the harness from relay to glow plugs for damage or loose connections.
- Controller settings: Ensure preheat duration and temperature thresholds are correctly set for the engine model.
Advertisements
Repair Difficulty
Medium
3/5