Low Fuel Pressure
Honeywell Fuel supply pressure below minimum threshold

Controller displays 'Low Fuel Pressure' or similar fuel pressure alarm and the generator will not run or drops out under load.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Partially closed gas shutoff valve, Clogged fuel filter or debris in fuel inlet, Failing LP/NG regulator, Excessive demand from other gas appliances on same line

How to Fix / Troubleshooting

Safety first: Turn the generator OFF and open the main breaker to the generator. Shut off gas before disconnecting any fittings. Work with a licensed gas technician when in doubt.

Steps:

  • Verify valves: Confirm all manual gas shutoff valves between the meter/tank and the generator are fully open.
  • Check for competing loads: If other large gas appliances (furnace, pool heater, etc.) are running, turn them off and see if the generator can start and run. If it does, the gas system may be undersized.
  • Inspect fuel filter and inlet: Locate the fuel inlet screen or filter at the generator. Shut off gas, remove the fitting, and inspect for rust, oil, or debris. Clean or replace as needed.
  • Examine regulator: Inspect the Honeywell fuel regulator for signs of failure (leaking, frost, whistling, or erratic operation). Replace if suspect.
  • Reset and test: Restore gas, leak-test all joints with a soap solution, then clear the alarm on the controller and run a manual test under load.
Advertisements

Repair Difficulty

Hard 4/5

Required Part

Fuel Regulator
Check Price on Amazon

We may earn a commission from links on this page.

Advertisements