E15
Hyundai Power Products Mains Voltage Abnormal / Grid Monitoring Fault

Controller displays E15, generator stops shortly after start, mains is present

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Incorrect mains sensing wiring to controller, Out-of-range utility voltage or frequency, Faulty mains voltage sensing circuit, Loose neutral on mains sensing

How to Fix / Troubleshooting

Safety first: Isolate the ATS and follow lockout/tagout procedures. Work on mains circuits only if you are qualified.

  • Check mains sensing terminals: On the Hyundai controller, verify that the mains sensing inputs (often labeled U, V, W, N or similar) are wired correctly from the ATS or mains supply.
  • Measure mains parameters: With a multimeter, confirm that mains voltage and frequency are within the acceptable range specified in the Hyundai manual. If the grid is unstable, the generator may refuse to transfer.
  • Inspect neutral: Ensure the mains neutral conductor is solidly connected to the controller sensing circuit. A floating neutral can cause false E15 alarms.
  • Controller test: If wiring and mains values are correct, the controller's mains sensing circuit may be faulty. Replacement of the controller module may be required.
Advertisements

Repair Difficulty

Professional Required 5/5

Required Part

Generator Controller Module
Check Price on Amazon

We may earn a commission from links on this page.