Hyundai Power
Failure to Stop / Return to Utility
Generator fails to shut down after utility power is restored; continues running in AUTO.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
ATS not signaling return to utility, Stuck Hyundai Power run relay, Controller configuration error, Faulty utility voltage sensing
How to Fix / Troubleshooting
Safety first: Confirm that utility power is stable and within normal limits before forcing shutdown.
- Check ATS operation: Verify that the ATS has transferred load back to utility. If not, troubleshoot the ATS first.
- Utility sensing: Measure utility voltage at the controller sensing terminals. If present but not recognized, the sensing circuit may be faulty.
- Run relay: Inspect the run relay in the control box for contacts welded closed. Replace the Hyundai Power relay if it does not release when commanded.
- Controller settings: Ensure stop delay and cool-down timers are correctly set. Reset to factory defaults if necessary.
- Manual stop: Use the OFF position to stop the generator until the automatic stop function is repaired.
Advertisements
Repair Difficulty
Hard
4/5