E17
JCB Mains Sensing / ATS Feedback Fault

E17 displayed; controller indicates mains failure input fault or ATS feedback error.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Incorrect mains voltage sensing wiring, Blown fuses in sensing circuit, Faulty ATS auxiliary contacts, Controller configuration error

How to Fix / Troubleshooting

Safety: Mains voltage is lethal. Only qualified personnel should work on mains sensing circuits.

  • Check controller readings: View mains voltage and frequency on the JCB controller. If zero or incorrect, suspect sensing wiring or fuses.
  • Inspect sensing fuses: In the control panel, locate and test fuses protecting the mains sensing lines.
  • Verify wiring: Compare the mains sensing connections to the JCB wiring diagram. Ensure each phase and neutral (if used) is correctly landed.
  • ATS feedback: Check auxiliary contacts on the ATS that signal position (mains/generator) back to the controller. Replace faulty aux contacts.
  • Configuration: Confirm controller parameters for mains voltage and frequency thresholds are set correctly for the site supply.
Advertisements

Repair Difficulty

Hard 4/5

Required Part

ATS Auxiliary Contact Block
Check Price on Amazon

We may earn a commission from links on this page.

Advertisements