Kubota No-Start Condition Without Fault Code

Kubota standby generator cranks normally but will not start; no error code is displayed on the controller.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Fuel shutoff solenoid not energizing, Air in fuel system, Weak compression due to engine wear, Incorrect starting procedure or disabled auto mode

How to Fix / Troubleshooting

Safety first: Ensure the generator is in OFF mode and cannot auto-start unexpectedly while you work.

  • Verify controller mode: Confirm the Kubota controller is in MANUAL or AUTO as required and that no start inhibit timers are active.
  • Check fuel shutoff solenoid: With an assistant cranking the engine, feel or listen for the click of the fuel shutoff solenoid at the injection pump. Measure voltage at its connector; if no voltage, trace wiring back to the controller. If voltage is present but the plunger does not move, replace the solenoid.
  • Bleed fuel system: Open bleed screws on the fuel filter and injection pump and use the hand primer until fuel is free of air. Tighten screws and retry starting.
  • Check air intake: Ensure the air filter is not completely blocked and that the intake duct is clear.
  • Compression check: If the engine cranks quickly with no smoke and never attempts to fire, a compression test may be needed to rule out internal engine wear (technician recommended).
Advertisements

Repair Difficulty

Medium 3/5

Required Part

Fuel Shutoff Solenoid
Check Price on Amazon