E03
Lifan Low Battery Voltage / Battery Fault

Lifan standby generator cranks but does not start and the controller shows E03.

Advertisements

Possible Causes

Discharged starting battery, Sulfated or failed battery, Faulty battery charger module, Loose or corroded battery terminals

How to Fix / Troubleshooting

Safety first: Turn the generator OFF and isolate from utility power. Wear eye protection when working around batteries.

  • Inspect battery connections: Check the positive and negative terminals on the Lifan starting battery. Clean any white/green corrosion with a baking soda and water solution, then tighten the clamps securely.
  • Measure battery voltage: With a multimeter, measure across the battery posts. A healthy fully charged 12 V battery should read about 12.6–12.8 V with the engine off. If below 12.0 V, charge the battery with an external charger.
  • Load test the battery: If available, use a battery load tester. If voltage drops excessively under load, replace the starting battery with one that meets Lifan’s cold cranking amp (CCA) specification.
  • Check built-in charger: With AC utility present and generator off, measure voltage at the battery. It should be around 13.2–13.8 V if the Lifan battery charger module is working. If it remains at static battery voltage, inspect the charger fuse and wiring. Replace the battery charger module if no output is present.
  • Clear code and test: After correcting battery and charger issues, reconnect everything, clear the E03 by cycling controller power, and attempt a manual start.
Advertisements

Repair Difficulty

Easy 2/5

Required Part

Starting Battery
Check Price on Amazon

We may earn a commission from links on this page.

Advertisements