F09
MTU Onsite Energy High DC Battery Voltage / Overcharge

Controller displays F09 – Battery voltage high, charger fault

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Battery charger voltage regulator failure, Incorrect charger settings, Loose battery sense wiring, Wrong charger model installed

How to Fix / Troubleshooting

Safety first: Overcharging can cause batteries to vent gas. Ensure good ventilation and avoid sparks or flames.

  • Measure DC voltage: Use a multimeter to confirm the actual battery voltage at the terminals. Compare to MTU’s specified float voltage.
  • Inspect charger settings: On the MTU battery charger, verify that the output voltage and battery type settings match the installed batteries. Adjust if necessary.
  • Check sense leads: If the charger uses remote sense wires, ensure they are correctly connected and not open or reversed.
  • Replace faulty charger: If voltage remains above specification with correct settings, replace the charger with an MTU-approved model.
  • Inspect batteries: Check batteries for swelling, excessive gassing, or electrolyte loss. Replace any damaged batteries.
  • Reset alarm: After voltage is stabilized, clear the F09 alarm and monitor battery voltage over several hours.
Advertisements

Repair Difficulty

Medium 3/5

Required Part

Battery Charger
Check Price on Amazon

We may earn a commission from links on this page.

Advertisements