F30
MTU Onsite Energy High Generator Bearing Temperature

Controller displays F30 – Generator bearing temperature high alarm

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Insufficient bearing lubrication, Bearing wear or damage, Misalignment between engine and generator, Faulty bearing temperature sensor

How to Fix / Troubleshooting

Safety first: Allow the generator to cool before touching bearing housings. Lock out the system.

  • Check temperature: Use an infrared thermometer to verify bearing housing temperature and compare with controller readings.
  • Inspect lubrication: For grease-lubricated bearings, check for signs of dried or contaminated grease. Re-lubricate according to MTU guidelines if applicable.
  • Alignment check: Inspect coupling alignment between engine and generator. Misalignment can cause bearing overheating and should be corrected by qualified personnel.
  • Sensor verification: Test the bearing temperature sensor and wiring. Replace if it is giving false high readings.
  • Professional service: If actual bearing temperature is high, schedule bearing inspection or replacement to prevent catastrophic failure.
Advertisements

Repair Difficulty

Professional Required 5/5

Required Part

Generator Bearing Temperature Sensor
Check Price on Amazon