Code 25
Onan High Exhaust Temperature Shutdown

Generator shuts down; Code 25 displayed indicating high exhaust temperature

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Restricted exhaust system or muffler, Overloaded generator causing high combustion temperatures, Lean fuel mixture due to fuel restriction, Faulty exhaust temperature sensor

How to Fix / Troubleshooting

Safety first: Exhaust components are extremely hot. Allow the unit to cool fully before inspection. Ensure adequate ventilation around the generator.

  • Reduce load: Open the main breaker and restart. If Code 25 does not reoccur with no load, gradually add loads and keep total load within the generator’s rated capacity.
  • Inspect exhaust system: Check for crushed exhaust pipes, blocked muffler outlets, or foreign objects near the exhaust outlet. Clear any obstructions.
  • Check air filter and fuel filter: Replace a dirty air filter and clogged fuel filter. Poor airflow or fuel restriction can alter combustion and raise exhaust temperature.
  • Inspect exhaust temperature sensor: Locate the sensor on the exhaust manifold or pipe. Check wiring and connector for heat damage. Replace the sensor if wiring is intact but Code 25 persists without actual overheating.
Advertisements

Repair Difficulty

Hard 4/5

Required Part

Exhaust Temperature Sensor
Check Price on Amazon

We may earn a commission from links on this page.