Code 37
Onan
Phase Voltage Imbalance / Phase Loss
Generator shuts down; Code 37 displayed indicating voltage imbalance or phase error (3-phase units)
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Loose or burned connection on one phase, Open stator winding on one phase, Unbalanced load across phases, Faulty voltage regulator sensing
How to Fix / Troubleshooting
Safety first: Three-phase systems carry dangerous voltages. Open the main breaker, disable auto-start, and use appropriate PPE. Only qualified personnel should work inside the power section.
- Measure phase voltages: With the generator running unloaded, measure voltage between all phase pairs and to neutral (if present). Values should be balanced within manufacturer limits.
- Inspect connections: Tighten all phase lugs and inspect for discoloration or melted insulation indicating overheating.
- Check load balance: Review connected loads in the transfer switch or panel. Redistribute loads to balance current draw across phases.
- Stator and regulator: If one phase is low or missing with good connections, the stator winding or regulator may be faulty and require professional replacement.
Advertisements
Repair Difficulty
Professional Required
5/5
Required Part
Alternator Stator
Check Price on Amazon