E012
Perkins Low DC Battery Voltage Alarm

Perkins generator controller displays E012 and indicates battery voltage low

Advertisements

Possible Causes

Aged or sulfated starting batteries, Faulty battery charger, Loose battery connections, Parasitic drain from control circuits

How to Fix / Troubleshooting

Safety: Wear eye protection when working around batteries. Avoid sparks and open flames.

  • Measure battery voltage: With the engine stopped, measure across the battery terminals. Compare to nominal values (12 V or 24 V system). If low, attempt to charge with an external charger.
  • Inspect charger: Check the panel‑mounted battery charger (often 230/120 V AC input). Verify AC supply is present and indicator LEDs show normal operation. Measure charger output voltage at the battery.
  • Clean and tighten terminals: Remove corrosion from posts and lugs using a wire brush. Refit and tighten securely. Apply a light coat of dielectric grease.
  • Load test batteries: Use a battery load tester to assess capacity. Replace batteries that cannot maintain voltage under load with the correct CCA rating for the Perkins engine.
  • Controller settings: Confirm the low‑voltage alarm threshold in the controller matches the system design. Adjust if incorrectly set.