E021
Perkins Generator Earth Fault / Ground Fault Detection

Perkins generator controller shows E021 and indicates earth fault / ground fault

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Insulation breakdown in alternator windings, Damaged power cable insulation to load, Moisture ingress in terminal box, Incorrect neutral‑earth bonding

How to Fix / Troubleshooting

Safety: Ground faults can be hazardous. Only qualified personnel should work on live power circuits. Isolate the generator and lock out before testing.

  • Visual inspection: Examine the alternator terminal box, busbars, and outgoing cables for signs of tracking, burn marks, or damaged insulation.
  • Insulation resistance test: With the generator isolated, use a megohmmeter to test insulation resistance between each phase and earth, and neutral to earth. Compare readings to manufacturer minimums.
  • Check for moisture: Look for condensation or water ingress in the alternator and junction boxes. Dry components thoroughly and improve sealing if necessary.
  • Neutral‑earth bond: Verify that neutral‑earth bonding is configured as per system design. Incorrect bonding can cause nuisance earth fault trips.
  • Repair or replace damaged components: Replace any cables or alternator components with low insulation resistance. Serious alternator faults may require rewinding or replacement of the alternator stator.