E17
Pramac
Safety Circuit Open (Door Switch / Guard Switch)
Pramac generator shows E17 and will not crank
Advertisements
Possible Causes
Service door or panel not fully closed, Faulty door safety switch, Broken wiring in safety loop, Bypassed or miswired safety contacts
How to Fix / Troubleshooting
Safety first: Never bypass safety switches for normal operation. They protect against contact with moving and live parts.
- Close all panels: Ensure all access doors and service panels on the Pramac enclosure are fully closed and latched.
- Inspect door switches: Locate the magnetic or mechanical door switches. Check alignment between switch and actuator. Adjust mounting if necessary.
- Check continuity: With power off, test continuity through the safety loop from the controller terminals. Repair or replace any open switches or damaged wiring.
- Clear alarm: After restoring the safety circuit, clear E17 and test start.
Advertisements
Repair Difficulty
Easy
2/5
Required Part
Door Safety Switch
Check Price on Amazon
We may earn a commission from links on this page.
Advertisements