Pramac
Load Transfer Failure
Generator starts and runs but ATS does not transfer load
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
ATS contactor coil failure, Mechanical jam in ATS, Incorrect voltage sensing at ATS, Interlock preventing transfer
How to Fix / Troubleshooting
Safety first: Work only with both mains and generator sources isolated and locked out. High voltage and backfeed hazards exist.
- Verify generator voltage: Confirm correct voltage and frequency at the ATS generator input terminals.
- Listen for ATS operation: During a test, listen for the contactor pulling in. No sound suggests a coil or control issue.
- Inspect ATS mechanism: With power off, manually operate the contactor (if design allows) to check for mechanical binding.
- Check control fuses and coils: Test the contactor coil for continuity and verify control fuses are intact. Replace faulty components with Pramac-specified parts.