AL11
SDMO Low Fuel Pressure Shutdown

Generator stops with AL11 indicating low fuel pressure or fuel supply fault.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Clogged SDMO fuel filter, Failing fuel lift pump, Air leaks on suction side, Blocked fuel tank vent

How to Fix / Troubleshooting

Safety first: Turn the generator OFF and isolate it from load. Avoid open flames when working with fuel.

  • Replace fuel filters: Change the primary and secondary fuel filters with SDMO-approved elements. Bleed the system thoroughly.
  • Inspect fuel lines and fittings: Check for loose clamps, cracked hoses, or damp spots indicating leaks. Tighten or replace as necessary, especially on the suction side.
  • Test lift pump: On mechanical pumps, operate the manual lever and confirm strong fuel flow. On electric pumps, verify voltage supply and listen for operation. Replace the pump if weak or inoperative.
  • Check tank vent: Ensure the fuel tank vent is not blocked. A blocked vent can cause vacuum and low fuel pressure. Clean or replace the vent fitting.
  • Reset AL11: After repairs, clear the alarm and run the generator under load to confirm stable operation.
Advertisements

Repair Difficulty

Medium 3/5

Required Part

Fuel Lift Pump
Check Price on Amazon