E08
Wacker Neuson Overvoltage Protection Trip

Controller shows E08 and prevents generator from connecting to load

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Faulty automatic voltage regulator (AVR), Incorrect AVR sensing wiring, Loose or corroded neutral/phase connections, Defective controller voltage sensing circuit

How to Fix / Troubleshooting

Safety first: Isolate the generator from the building transfer switch. Turn OFF the main breaker on the generator before working inside the control panel.

  • Visual inspection: Open the control panel and inspect the AVR module and wiring harness. Look for burnt components, discoloration, or melted insulation.
  • Check terminal tightness: Tighten all phase and neutral terminals on the generator output block and AVR sensing leads. Loose connections can cause unstable voltage readings.
  • Measure output voltage: In MANUAL mode with no load and main breaker OFF, measure line-to-line and line-to-neutral voltages. If significantly above rated (e.g., >260 V on a 230 V system), the AVR is likely faulty.
  • Inspect sensing wires: Ensure the AVR sensing wires are connected to the correct phases and neutral as per the Wacker Neuson wiring diagram. Miswiring can cause overvoltage.
  • Replace AVR if needed: If voltage remains high with correct wiring, replace the AVR with the exact Wacker Neuson-specified part number.
  • Reset and test: Clear E08, re-test voltage, and only then re-energize the main breaker and transfer switch.