Wacker Neuson Automatic Transfer Switch (ATS) Fails to Transfer Load

Generator runs but does not transfer power to the building; no error code displayed

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Defective ATS contactor, Failed ATS control coil, Miswired ATS control circuit from generator, Mechanical binding in transfer mechanism

How to Fix / Troubleshooting

Safety first: This involves work on high-voltage equipment. Only qualified personnel should open the ATS. Isolate both utility and generator sources and verify de-energized before touching internal parts.

  • Check generator output: Confirm the generator is producing correct voltage and frequency at its terminals with a multimeter.
  • Verify ATS control signal: Check that the Wacker Neuson controller is sending a transfer signal (dry contact closure or voltage) to the ATS when in AUTO and utility is absent.
  • Inspect ATS mechanism: With power off, manually operate the transfer mechanism (if provisioned). Ensure it moves freely and latches in both positions.
  • Test contactor coil: Measure coil resistance and verify it energizes when the transfer signal is present. Replace the contactor if the coil is open or the contacts are burnt.
  • Check interlocks: Verify any mechanical or electrical interlocks are not preventing transfer.
  • Restore service: After repairs, test a full transfer sequence under supervision.