Possible Causes
Governor linkage wear or sticking, Air in fuel system, Partially clogged fuel filter, Incorrect governor spring tension
How to Fix / Troubleshooting
Safety first: Keep clear of moving linkages and belts while the engine is running. Disable AUTO mode before adjustments.
- Inspect linkage: With the engine off, move the governor and throttle linkages by hand. Clean and lightly lubricate pivot points if stiff.
- Replace fuel filter: Install a new OEM fuel filter to eliminate restriction as a cause.
- Bleed fuel system: On diesel units, bleed air from the filter and injection pump according to the manual.
- Adjust governor: Follow the Wacker Neuson service procedure to set governor spring tension and idle/no-load speed. Small adjustments can stabilize hunting.
- Test under load: Run the generator with a moderate load and observe frequency stability.