E11
Winco Phase Loss / Phase Imbalance Fault

Controller shows E11 / PHASE LOSS or PHASE IMBALANCE on three-phase Winco standby generator.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Open phase in generator stator winding, Loose phase conductor in terminal block, Faulty transfer switch contact on one phase, Blown line fuse (if equipped)

How to Fix / Troubleshooting

Safety first: Open all breakers and lock out/tag out. Three-phase systems carry lethal voltages.

  • Visual inspection: With power off, inspect the generator terminal block and transfer switch lugs for loose or burned connections on any phase.
  • Check fuses and breakers: If the system uses line fuses, test each with a meter and replace any open fuses with the correct rating.
  • Measure phase voltages: Have a qualified person measure voltage between all phase pairs and to neutral. A missing or low phase indicates a stator or connection issue.

Phase loss often requires stator or transfer switch repair by a professional. Do not operate with a missing phase.

Advertisements

Repair Difficulty

Professional Required 5/5

Required Part

Stator Assembly
Check Price on Amazon

We may earn a commission from links on this page.

Advertisements