E13
Winco
Emergency Stop Circuit Open
Controller shows E13 / EMERGENCY STOP ACTIVE and the generator will not start.
Advertisements
Possible Causes
Emergency stop pushbutton engaged, Open E-stop wiring in control circuit, Faulty emergency stop switch, Loose terminal at controller E-stop input
How to Fix / Troubleshooting
Safety first: Confirm that no emergency condition exists before resetting any E-stop.
- Reset E-stop: Locate the red emergency stop pushbutton on the Winco generator enclosure. Twist or pull to reset, depending on design.
- Inspect wiring: Check the low-voltage control wiring from the E-stop to the controller for damage, loose terminals, or corrosion.
- Test switch: With power off, use a meter to verify continuity through the E-stop switch when reset. Replace if it does not close properly.
After restoring the E-stop circuit, clear the E13 code and test a manual start.
Advertisements
Repair Difficulty
Easy
2/5
Required Part
Emergency Stop Switch
Check Price on Amazon
We may earn a commission from links on this page.