Possible Causes

Incorrect utility sensing thresholds, Loose utility sense wiring, Faulty controller utility sense input, Unstable utility voltage

How to Fix / Troubleshooting

Safety first: Disable AUTO to stop cycling while troubleshooting.

  • Check utility voltage: Have utility voltage measured at the transfer switch. Large fluctuations may cause the controller to think power is failing.
  • Inspect sense wiring: Verify the utility sense leads from the transfer switch to the Winco controller are tight and correctly landed.
  • Controller settings: Confirm utility dropout and pickup voltage settings in the controller match Winco specifications.

If cycling continues with stable utility, controller or sense circuit service is required.