Possible Causes
Oversized ACV burner for system load, Incorrect control settings (differential too small), Poor primary flow, Sensor placement issues
How to Fix / Troubleshooting
Safety: Adjust control parameters only within ACV guidelines.
- 1. Check temperature differential: In the installer menu, increase the on/off differential or anti-cycling time if available.
- 2. Improve flow: Ensure primary pump speed is adequate and all valves are open to allow good circulation.
- 3. Sensor placement: Verify that sensors are correctly installed in their pockets and not influenced by local hot spots.
- 4. Hydraulic balancing: Have a heating engineer balance the system to provide a more stable load.
Persistent short cycling can reduce efficiency and lifespan; consider system redesign if the heater is significantly oversized.