E09
Alpha
Condensate Drain Blockage
Unit shows E09 and shuts down; may be accompanied by gurgling sounds in the vent or condensate lines.
Advertisements
Possible Causes
Clogged condensate trap, Blocked condensate drain hose, Frozen condensate line, Improper condensate routing
How to Fix / Troubleshooting
Safety: Turn OFF power. Avoid spilling condensate on electrical components.
- Locate condensate trap: Find the Alpha condensate trap at the bottom of the heat exchanger or flue collector.
- Inspect and clean: Remove the trap following Alpha instructions. Flush it with clean water to remove sludge or debris. Ensure the internal float (if present) moves freely.
- Check drain hose: Verify the condensate hose slopes continuously downward to the drain and is not kinked or frozen. Clear any blockage with a flexible brush or by flushing with water.
- Reassemble and test: Reinstall the trap, restore power, and run the unit. Watch for leaks and confirm E09 clears.
If condensate repeatedly backs up, have the drain system and venting evaluated by a professional.