E11
Chaffoteaux
Gas Valve Control / Modulation Fault
E11 error, unit may start then shut down; sometimes linked to gas valve control.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Defective gas valve coil, Loose gas valve connector, Faulty PCB gas control circuit, Incorrect gas type configuration
How to Fix / Troubleshooting
Safety: Isolate gas and power. Only qualified gas engineers should work on gas valves.
- Check gas valve connector: Access the gas valve and ensure the electrical plug is fully seated and free from corrosion.
- Measure coil resistance: With the appliance isolated, disconnect the gas valve and measure the resistance of the modulation coil(s). Compare with service manual values. Replace the valve if readings are out of range.
- Verify correct gas type setting: Ensure the appliance is configured for the correct gas (natural gas or LPG) as per the data plate. Incorrect configuration can cause modulation errors.
- PCB check: If the gas valve tests OK, the PCB may not be providing correct control voltage and should be tested/replaced by a professional.
Do not attempt to adjust gas rate or internal valve settings without proper training and equipment.
Advertisements
Repair Difficulty
Professional Required