A07
Nibe Outdoor Temperature Sensor Fault

Display shows A07; water heater may shut down and indicate outdoor sensor fault (for systems using outdoor compensation).

Advertisements

Possible Causes

Outdoor sensor cable cut or shorted, sensor exposed to direct sun or incorrect mounting, failed NTC element, loose terminal connection on control board

How to Fix / Troubleshooting

Safety first: Turn off power before working on sensor wiring.

The outdoor sensor is used for weather-compensated control in some Nibe systems.

  • Step 1 – Inspect outdoor sensor:
    • Locate the sensor on an external wall (north or shaded side recommended).
    • Check that the housing is intact and not filled with water or insects.
  • Step 2 – Check cable:
    • Inspect the cable run for damage from UV, animals, or mechanical impact.
    • Ensure the cable is firmly connected at the control board terminals.
  • Step 3 – Sensor test:
    • With power off, disconnect the sensor and measure resistance.
    • Compare to Nibe’s NTC table for the current outdoor temperature.
  • Step 4 – Reset and verify:
    • Restore power and clear the alarm.
    • Confirm that the displayed outdoor temperature is realistic.

If the sensor is faulty, replace it with a genuine Nibe outdoor sensor to ensure correct curve control.