Weil-McLain Continuous DHW Call

Weil-McLain indirect water heater causes boiler to run constantly, even when no hot water is being used.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Stuck tank aquastat contacts, Shorted tank sensor wiring, Miswired control terminals, Leaking hot water recirculation loop

How to Fix / Troubleshooting

Safety first: Turn off power before working on control wiring.

  • Check tank temperature: Feel the tank shell or use a thermometer at a faucet. If water is already at or above setpoint but boiler still runs for DHW, the control is not sensing correctly.
  • Inspect aquastat or sensor: For mechanical aquastats, tap the control lightly; if the boiler shuts off, the contacts may be sticking and need replacement. For sensors, inspect wiring for shorts.
  • Verify wiring: Confirm that DHW call terminals on the boiler control are wired only to the tank control, not accidentally tied to space heating calls.
  • Check recirculation loop: A constantly circulating hot water loop without proper controls can keep the tank calling for heat. Install or repair recirculation controls as needed.