E1 332
Worcester Bosch Flame Signal / Combustion Quality Fault

Boiler displays E1 332, may run briefly then shut down, often associated with incorrect combustion.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Incorrect gas/air ratio, Blocked or partially blocked burner, Faulty ionisation electrode, Faulty gas valve modulation control

How to Fix / Troubleshooting

Safety first: This is a combustion-related fault. Only a Gas Safe engineer with a calibrated flue gas analyser should adjust combustion or gas valves.

Engineer procedure:

  • Check the burner for contamination, rust, or debris; clean or replace the burner as required.
  • Inspect and clean the ionisation electrode and ignition electrodes; ensure correct positioning and gap.
  • Perform a full combustion analysis at minimum and maximum rate, adjusting the gas valve modulation (where permitted) to achieve values specified by Worcester Bosch.
  • Verify the condensate trap and siphon are clear to prevent flue gas recirculation.
  • If combustion cannot be set correctly, replace the gas valve and re-commission.
Advertisements

Repair Difficulty

Professional Required 5/5

Required Part

Burner Assembly