E06
Dettson Return Temperature Sensor Fault

Boiler shows E06 and shuts down shortly after starting

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Open or shorted Dettson return NTC sensor, Loose sensor wiring harness, Sensor not properly seated on return pipe, Control board input failure

How to Fix / Troubleshooting

Safety: Turn off power before accessing internal wiring or sensors.

  • Locate return sensor: On Dettson boilers, the return temperature sensor (NTC) is typically clipped or strapped to the return water pipe or inserted into a well.
  • Inspect wiring: Check the sensor cable for cuts, abrasions, or pulled connectors. Reseat the plug at the control board and at the sensor if applicable.
  • Check sensor mounting: Ensure the sensor is firmly attached to the pipe with good thermal contact and insulated if required by the manual. A loose sensor can give erratic readings.
  • Resistance test (for technicians): A professional can measure sensor resistance at room temperature and compare it to Dettson specifications. If out of range, replace the sensor.
  • Control board: If a known-good sensor still triggers E06, the boiler control board may have a defective sensor input and will need replacement by a qualified technician.
Advertisements

Repair Difficulty

Medium 3/5

Required Part

Dettson return temperature sensor (NTC)