LO
Frigidaire
Low Ambient Temperature Protection
Dehumidifier displays LO and does not start dehumidifying; may run fan only.
Advertisements
Possible Causes
Room temperature below operating range, Faulty ambient temperature sensor reading too low, Unit placed near cold draft or exterior wall, Control board miscalibration
How to Fix / Troubleshooting
Note: LO is often informational, indicating the room is too cold for safe operation.
Steps:
- Check room temperature: Use a separate thermometer to verify the room is above 41°F / 5°C. If not, move the unit to a warmer area.
- Avoid cold drafts: Do not place the unit directly on a cold concrete floor or next to an exterior door or window where cold air can affect the sensor.
- Power reset: Unplug for 5 minutes, then plug back in and check if LO clears in a warmer environment.
- Sensor check: If the room is clearly warm (e.g., 70°F / 21°C) but LO remains, inspect the ambient temperature sensor and its wiring for damage or dislodging.
- Replace sensor if needed: A faulty ambient thermistor can falsely report low temperature and should be replaced.
Advertisements
Repair Difficulty
Easy
2/5
Required Part
Ambient Temperature Sensor (Thermistor)
Check Price on Amazon