E-15
CAT Remote Start Signal Fault / ATS Communication Error

Controller displays E-15, generator will not start automatically

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Open remote start wiring from ATS, Incorrect dry contact wiring, Faulty ATS control board, Controller input failure

How to Fix / Troubleshooting

Safety: Disable automatic start and lock out the transfer switch before working on control wiring.

  • Check controller mode: Ensure the CAT controller is in AUTO mode. In OFF or MANUAL, it will not respond to remote start.
  • Inspect remote start terminals: Locate the remote start input terminals on the generator controller. Verify that the wires from the ATS are secure and not corroded.
  • Test remote start contact: At the generator, temporarily jumper the remote start terminals (per CAT instructions) to simulate a start signal. If the generator starts, the issue is in the ATS or wiring.
  • Check ATS control board: Inspect the ATS for blown fuses, tripped control power breakers, or alarm LEDs. Reset as needed and verify the ATS sends a start signal when utility fails (simulate only if safe and per procedure).
  • Remove jumper and restore wiring: After testing, remove any temporary jumpers and reconnect the ATS wiring correctly.

If E-15 persists with known-good wiring and ATS operation, the controller input may be defective and require replacement by a CAT technician.