CAT Auto Start Logic / Scheduling Fault

Generator fails to start automatically during a utility outage but starts manually

Advertisements

Possible Causes

Controller not in AUTO mode, Exercise schedule misconfigured, ATS start signal not reaching controller, Disabled auto-start setting

How to Fix / Troubleshooting

Safety: Be aware that restoring AUTO mode can cause an unexpected start. Ensure the area is clear.

  • Check controller mode: Confirm the CAT controller is set to AUTO, not OFF or MANUAL.
  • Review settings: Navigate the controller menus to verify that auto-start and exercise functions are enabled and correctly scheduled.
  • Test ATS start signal: Simulate a utility failure (per CAT and site procedures) and check if the controller logs a start request. If not, inspect the start signal wiring from the ATS.

If the generator starts manually but never automatically despite correct settings and wiring, the controller or ATS logic may be faulty and should be checked by a technician.

Advertisements

Repair Difficulty

Easy 2/5

Required Part

Generator Controller
Check Price on Amazon

We may earn a commission from links on this page.

Advertisements